Power Flow Configuration     

Configure the distribution of power flow through each component in the system.

 
Infeed Power Distribution
  • Continuous Power
    • Divided equally
      • In a system with two drives, Drive 1 and Drive 2 each share 50% of the system continuous power requirement
    • Proportional to continuous power rating
      • If Drive 1 has twice the continuous rating of Drive 2, then Drive 1 and Drive 2 bear 66% and 33% respectively of the system continuous power requirement
  • Peak Power
    • Same as continuous power
    • System peak power requirement
      • Sets the application system peak power requirement as the peak power requirement for each drive/infeed

 

Bleeder Power Distribution

  • Continuous Power
    • Divided equally
      • In a system with two bleeders, Bleeder 1 and Bleeder 2 each share 50% of the system continuous bleeder power requirement
    • Proportional to continuous power rating
      • If Bleeder 1 has twice the continuous rating of Bleeder 2, then Bleeder 1 and Bleeder 2 bear 66% and 33% respectively of the system continuous bleeder power requirement
    • Proportional to resistor current
      • Based on resistor current (Vdc/R)
      • Put another way, inversely proportional to resistor ohms
  • Peak Power
    • Same as continuous power
    • System peak power requirement
      • Sets the application system peak power requirement as the peak power requirement for each drive/infeed